Product category: | insulated and sheathed wires |
---|---|
Type: | SIENOPYR-PLUS E30 JE-H(St)H FE180 |
Conductor material: | CU |
No. of cores: | 32 |
Cross-section: | 2x0.8 mm² |
Core insulation material: | LSOH |
Outer jacket material: | LSOH |
Nominal outer diameter: | 19.5 mm |
Approx. weight: | 580 kg/km |
Appplication: | adatátvitel |
Construction: | Conductor material bare copper; conductor shape round (R); conductor class class 1, solid (E); Insulation zero halogen elastomeric compound; core assembly 4 pairs in sub-units, sub-units in layers; sub-unit identification each bundle consiting of 4 pairs is identified by numbered tape electrostatic screen electrostatic shield of aluminium-bonded polyester tape and copper drain wire outer sheath flame retardant low smoke compound |
Standard: | DIN 4102-12 standard based on DIN VDE 0815 |
Available colours: | orange, red |
Fire performance: | Flame propagation DIN EN 60332-3-24, DIN EN 60332-1-2. Fire resistant characteristics FE180 according to DIN VDE 0472-814, 90 minutes according to IEC 60331-23 |
Halogen-free | |
Minimum installation temperature: | Laying min -5°C; fix inst. min -30°C max +70°C |
Application: | Cables with the trade mark SIENOPYR-PLUS E30 can be used in indoor installation. An installation in earth is not allowed. These cables are for data transmission. In accordance to DIN 4102-12 the SIENOPYR-PLUS E30 cables have circuit integrity in case of fire #30 minutes. SIENOPYR-PLUS E30 cables shall be installed in accordance to the certificates ( Allgemeine bauaufsichtliche Prüfzeugnisse - AbP). Zero halogene DIN EN 50267-2-2. |